When energy is cheap   you do n’t often   worry about the cost   of using heat for humidity control . This is because the   advantages of a good giving up and disease costless crop far   outweigh the cost of ensure humidity . However ,   when   the toll of muscularity increase , you   are leave   ask " Can I open to control humidity ? "

In 2008 gamy energy prices pass one greenhouse to take the view that active humidness control should be minimized that year . This may have left them exposed to potential disease problem ; so was it the proper determination ? In this article , Nathalie Key with AHDB describes a study they carried out on humidness control scheme .

A comparison of humidity strategies"We compare the performance of two indistinguishable greenhouses go under two different humidness control strategies – with optimize humidness control and with no dynamic humidness control . "

Article image

The size of it and layout of the nursery gave the researchers the unequaled opportunity to liken the performance of two monovular greenhouse manoeuvre under different humidity control strategies . They therefore did side by side comparisons of the undermentioned two feeler .

The graphical record in Figures 1 and 2 show the heating plant pipe temperatures and the climate in the two greenhouses on the same day .

Figure 1 : Greenhouse with humidity ascendency

Article image

Figure 2 : glasshouse without humidity control

" If we look at the night flow we can see that the greenhouse with humidity control had an median RH of 85 % compare to 90 % in the ‘ no control ’ greenhouse . However , to achieve this , the pipe temperature in the humidity control house was 10oC hotter . "

What does humidity control cost?“We calculate the cost of our optimized humidity restraint strategy and consider the potential advantages and value of such a scheme . "

Article image

Over the period of time from 16:00hrs to 08:00hrs :

Active humidity control required heating for the entire 14 hour at an average organ pipe temperature of 35o , and no humidity control used heating system for 12½ hours at an average pipe temperature of 21o

" We can use this information with data about the nursery temperature , warming pipe length and diam and boiler efficiency to reckon the heat used in each scenario . "

Article image

On this night the active humidity control used 0.7kWh / m2   more energy , cost an extra 1.75p / m2 . free-base on the flora tightness   of 9 plant / m2 ,   the cost of humidity control on this night was therefore 0.2p / flora .

Scenario comparison

However , do n’t assume that humidity control costs 0.2p / plant every nighttime . This was a bad case Nox with mild temperatures ; so humidness control was particularly difficult . On a colder dark more passion would have been call for to keep up the temperature in the ‘ no humidity control ’ block and the differences between the intervention would have been equaled out .